Controller provides control of protected facilities alarm loops with non-addressable security, fire and fire-and-security detectors installed therein.
Controller being a part of set of technical means of fire and security alarm and fire suppression control KTS-2000 is designed for control of protected facilities alarm loops with non-addressable security, fire and fire-and-security detectors installed therein, both when AL (alarm loop) is directly connected to controller and through remote modules via RS-485 interface; for transmission of alarm signals upon actuation of detectors or violation of AL communication line integrity (fault, short circuit) to light and sound alarms through relay outputs and to the mid/upper-level equipment (KTS-2000, PC) via RS-485/Ethernet interfaces; for digital signal control with a solid-state relay; for local and centralized control of protected areas, fire fighting and smoke removal units, voice announcement, control of engineering equipment and light and sound alarms.
General number of analogue inputs | 8 |
Number of digital signals inputs | 8 |
Number of AL analogue signals inputs | 4 |
Number of RS-485 ports | 2 |
Number of Ethernet ports | 12 independent |
2 independent ports | available |
Supported protocols: | |
RS-485 port | Modbus RTU |
Ethernet port | Modbus TCP |
Rate of exchange via RS-485 (bit/s): | 2400—307200 |
Rate of exchange via Ethernet (Mbit/s) | 010/100 |
Rated supply voltage (range), V | 24 (from 18 to 36) |
Current consumed current in standby mode, А, max. | 0.25 |
Ingress protection rating | IP20 |
Program memory size, kb | 256 |
Data memory size, byte | 8192 |
Operating temperature range | -40…+70°С |
Overall dimensions, mm, max. | 180x80x40 |
Weight, max. | 0.4 kg; |